Modbus to Optocontrol Forum - Published: Hello I have a PowerLogic Series 800 Power Meter that I would like to datalog my power data in Optodisplay. I downloaded and installed the OptoIntegration Toolkit to Optocontrol and was wondering if I...moreHello I have a PowerLogic Series 800 Power Meter that I would like to datalog my power data in Optodisplay. I downloaded and installed the OptoIntegration Toolkit to Optocontrol and was wondering if I could get some guidance on how to use it. I have a SNAP LCM4 controller that I would use to connect to the meter on COM 0. But once I connect to the meter I am confused on where and how to place the data so I can read it. I’ve been looking for a basic guideline on how to configure the Integration T...... <less BACnet Questions Forum - Published: I’ve been given a project to get Opto22 PAC Controllers talking to BACnet equipment. I’m slowly learning BACnet. I downloaded the Opto22 BACnet/IP integration kit and didn’t have much luck getting it...moreI’ve been given a project to get Opto22 PAC Controllers talking to BACnet equipment. I’m slowly learning BACnet. I downloaded the Opto22 BACnet/IP integration kit and didn’t have much luck getting it to work with my initial setup which includes a an Opto22 PAC R2, a Fieldserver router and a Johnson Controls stat. I then noticed the code submitted by Nick Stephens a few years ago and downloaded that to give it a try. He had posted two subroutines, one for discovery and one for reading multipl...... <less EPIC as DNP3 Server/Slave Forum - Published: Hi All, Before I begin, I want to clear up terminology based on my understanding. Master DNP3 = Client Slave DNP3 = Server/Outstation I know Opto22 has DNP3 integration but that is for SNAP PAC...moreHi All, Before I begin, I want to clear up terminology based on my understanding. Master DNP3 = Client Slave DNP3 = Server/Outstation I know Opto22 has DNP3 integration but that is for SNAP PAC only. This kit can make SNAP PAC as Master and Slave. While EPIC has Ignition Edge. Ignition Edge has DNP3 driver that I can install but it allows EPIC as Master only. (In configuration, when adding device it shown “connect to DNP3 outstation”). So, what route should I make to establish my EPIC as...... <less Modbus - getting multiple reads when I only want one Forum - Published: This is a tough one, but I know people smarter than me are here to help! Background and Configuration I have integrated Opto22’s Modbus Integration Kit ( http://www.opto22.com/site/downloads/dl...moreThis is a tough one, but I know people smarter than me are here to help! Background and Configuration I have integrated Opto22’s Modbus Integration Kit ( http://www.opto22.com/site/downloads/dl_drilldown.aspx?aid=4206 ) in the attached PAC Control Professional 9.6d project. For the modbus server, I am using “Modbus Server Pro” v3.3 for Mac, Modbus Server - AppHugs. To make the project run in your environment, you will need to change the string variables sIPPORT_CYCLOTRON and sIPPORT_TMS initia...... <less TCP Communication Problems on Upgrade Forum - Published: Communication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it...moreCommunication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it happens to be using the DNP Integration Kit via TCP Connections as a DNP Outstation. The problem is related to TCP connectivity and listening / receiving request via TCP ports verses the bulk of the DNP command / response configuration. When operating on 9.1f we had no issues receiving requests and ...... <less Leaving Communiation Handle Open Forum - Published: Sorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close...moreSorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close the communication. Would this cause problems If I were to keep calling the SR for new Modbus devices? I guess worst case for me would be 25. Eric... <less DNP3 Configuration for OPTO 22 (S2 and R2) with Schneider Elecetric - ClearSCADA Forum - Published: Hello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA...moreHello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA is the Master. I was able to start the initial communication with the following settings: //Load only the controller running the DNP3 Charts poPAC_DNP_Controller_SNAP_PAC_R2 = &SNAP_R2_8E78;//Load Pointer, This is the Controler With The DNP3 Charts nDNP_Outstation_Address = 20;//Set Outstation Ad...... <less Modbus Master & Slave Communication Forum - Published: Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?...Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?... <less Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
BACnet Questions Forum - Published: I’ve been given a project to get Opto22 PAC Controllers talking to BACnet equipment. I’m slowly learning BACnet. I downloaded the Opto22 BACnet/IP integration kit and didn’t have much luck getting it...moreI’ve been given a project to get Opto22 PAC Controllers talking to BACnet equipment. I’m slowly learning BACnet. I downloaded the Opto22 BACnet/IP integration kit and didn’t have much luck getting it to work with my initial setup which includes a an Opto22 PAC R2, a Fieldserver router and a Johnson Controls stat. I then noticed the code submitted by Nick Stephens a few years ago and downloaded that to give it a try. He had posted two subroutines, one for discovery and one for reading multipl...... <less EPIC as DNP3 Server/Slave Forum - Published: Hi All, Before I begin, I want to clear up terminology based on my understanding. Master DNP3 = Client Slave DNP3 = Server/Outstation I know Opto22 has DNP3 integration but that is for SNAP PAC...moreHi All, Before I begin, I want to clear up terminology based on my understanding. Master DNP3 = Client Slave DNP3 = Server/Outstation I know Opto22 has DNP3 integration but that is for SNAP PAC only. This kit can make SNAP PAC as Master and Slave. While EPIC has Ignition Edge. Ignition Edge has DNP3 driver that I can install but it allows EPIC as Master only. (In configuration, when adding device it shown “connect to DNP3 outstation”). So, what route should I make to establish my EPIC as...... <less Modbus - getting multiple reads when I only want one Forum - Published: This is a tough one, but I know people smarter than me are here to help! Background and Configuration I have integrated Opto22’s Modbus Integration Kit ( http://www.opto22.com/site/downloads/dl...moreThis is a tough one, but I know people smarter than me are here to help! Background and Configuration I have integrated Opto22’s Modbus Integration Kit ( http://www.opto22.com/site/downloads/dl_drilldown.aspx?aid=4206 ) in the attached PAC Control Professional 9.6d project. For the modbus server, I am using “Modbus Server Pro” v3.3 for Mac, Modbus Server - AppHugs. To make the project run in your environment, you will need to change the string variables sIPPORT_CYCLOTRON and sIPPORT_TMS initia...... <less TCP Communication Problems on Upgrade Forum - Published: Communication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it...moreCommunication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it happens to be using the DNP Integration Kit via TCP Connections as a DNP Outstation. The problem is related to TCP connectivity and listening / receiving request via TCP ports verses the bulk of the DNP command / response configuration. When operating on 9.1f we had no issues receiving requests and ...... <less Leaving Communiation Handle Open Forum - Published: Sorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close...moreSorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close the communication. Would this cause problems If I were to keep calling the SR for new Modbus devices? I guess worst case for me would be 25. Eric... <less DNP3 Configuration for OPTO 22 (S2 and R2) with Schneider Elecetric - ClearSCADA Forum - Published: Hello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA...moreHello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA is the Master. I was able to start the initial communication with the following settings: //Load only the controller running the DNP3 Charts poPAC_DNP_Controller_SNAP_PAC_R2 = &SNAP_R2_8E78;//Load Pointer, This is the Controler With The DNP3 Charts nDNP_Outstation_Address = 20;//Set Outstation Ad...... <less Modbus Master & Slave Communication Forum - Published: Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?...Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?... <less Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
EPIC as DNP3 Server/Slave Forum - Published: Hi All, Before I begin, I want to clear up terminology based on my understanding. Master DNP3 = Client Slave DNP3 = Server/Outstation I know Opto22 has DNP3 integration but that is for SNAP PAC...moreHi All, Before I begin, I want to clear up terminology based on my understanding. Master DNP3 = Client Slave DNP3 = Server/Outstation I know Opto22 has DNP3 integration but that is for SNAP PAC only. This kit can make SNAP PAC as Master and Slave. While EPIC has Ignition Edge. Ignition Edge has DNP3 driver that I can install but it allows EPIC as Master only. (In configuration, when adding device it shown “connect to DNP3 outstation”). So, what route should I make to establish my EPIC as...... <less Modbus - getting multiple reads when I only want one Forum - Published: This is a tough one, but I know people smarter than me are here to help! Background and Configuration I have integrated Opto22’s Modbus Integration Kit ( http://www.opto22.com/site/downloads/dl...moreThis is a tough one, but I know people smarter than me are here to help! Background and Configuration I have integrated Opto22’s Modbus Integration Kit ( http://www.opto22.com/site/downloads/dl_drilldown.aspx?aid=4206 ) in the attached PAC Control Professional 9.6d project. For the modbus server, I am using “Modbus Server Pro” v3.3 for Mac, Modbus Server - AppHugs. To make the project run in your environment, you will need to change the string variables sIPPORT_CYCLOTRON and sIPPORT_TMS initia...... <less TCP Communication Problems on Upgrade Forum - Published: Communication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it...moreCommunication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it happens to be using the DNP Integration Kit via TCP Connections as a DNP Outstation. The problem is related to TCP connectivity and listening / receiving request via TCP ports verses the bulk of the DNP command / response configuration. When operating on 9.1f we had no issues receiving requests and ...... <less Leaving Communiation Handle Open Forum - Published: Sorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close...moreSorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close the communication. Would this cause problems If I were to keep calling the SR for new Modbus devices? I guess worst case for me would be 25. Eric... <less DNP3 Configuration for OPTO 22 (S2 and R2) with Schneider Elecetric - ClearSCADA Forum - Published: Hello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA...moreHello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA is the Master. I was able to start the initial communication with the following settings: //Load only the controller running the DNP3 Charts poPAC_DNP_Controller_SNAP_PAC_R2 = &SNAP_R2_8E78;//Load Pointer, This is the Controler With The DNP3 Charts nDNP_Outstation_Address = 20;//Set Outstation Ad...... <less Modbus Master & Slave Communication Forum - Published: Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?...Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?... <less Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Modbus - getting multiple reads when I only want one Forum - Published: This is a tough one, but I know people smarter than me are here to help! Background and Configuration I have integrated Opto22’s Modbus Integration Kit ( http://www.opto22.com/site/downloads/dl...moreThis is a tough one, but I know people smarter than me are here to help! Background and Configuration I have integrated Opto22’s Modbus Integration Kit ( http://www.opto22.com/site/downloads/dl_drilldown.aspx?aid=4206 ) in the attached PAC Control Professional 9.6d project. For the modbus server, I am using “Modbus Server Pro” v3.3 for Mac, Modbus Server - AppHugs. To make the project run in your environment, you will need to change the string variables sIPPORT_CYCLOTRON and sIPPORT_TMS initia...... <less TCP Communication Problems on Upgrade Forum - Published: Communication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it...moreCommunication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it happens to be using the DNP Integration Kit via TCP Connections as a DNP Outstation. The problem is related to TCP connectivity and listening / receiving request via TCP ports verses the bulk of the DNP command / response configuration. When operating on 9.1f we had no issues receiving requests and ...... <less Leaving Communiation Handle Open Forum - Published: Sorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close...moreSorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close the communication. Would this cause problems If I were to keep calling the SR for new Modbus devices? I guess worst case for me would be 25. Eric... <less DNP3 Configuration for OPTO 22 (S2 and R2) with Schneider Elecetric - ClearSCADA Forum - Published: Hello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA...moreHello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA is the Master. I was able to start the initial communication with the following settings: //Load only the controller running the DNP3 Charts poPAC_DNP_Controller_SNAP_PAC_R2 = &SNAP_R2_8E78;//Load Pointer, This is the Controler With The DNP3 Charts nDNP_Outstation_Address = 20;//Set Outstation Ad...... <less Modbus Master & Slave Communication Forum - Published: Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?...Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?... <less Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
TCP Communication Problems on Upgrade Forum - Published: Communication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it...moreCommunication Problems on Firmware / Software Upgrade. Looking to see if anyone else has run into this problem. We recently upgraded a PAC-S2 from 9.1f to 10.4 (both Firmware and PACProject Pro) – it happens to be using the DNP Integration Kit via TCP Connections as a DNP Outstation. The problem is related to TCP connectivity and listening / receiving request via TCP ports verses the bulk of the DNP command / response configuration. When operating on 9.1f we had no issues receiving requests and ...... <less Leaving Communiation Handle Open Forum - Published: Sorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close...moreSorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close the communication. Would this cause problems If I were to keep calling the SR for new Modbus devices? I guess worst case for me would be 25. Eric... <less DNP3 Configuration for OPTO 22 (S2 and R2) with Schneider Elecetric - ClearSCADA Forum - Published: Hello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA...moreHello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA is the Master. I was able to start the initial communication with the following settings: //Load only the controller running the DNP3 Charts poPAC_DNP_Controller_SNAP_PAC_R2 = &SNAP_R2_8E78;//Load Pointer, This is the Controler With The DNP3 Charts nDNP_Outstation_Address = 20;//Set Outstation Ad...... <less Modbus Master & Slave Communication Forum - Published: Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?...Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?... <less Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Leaving Communiation Handle Open Forum - Published: Sorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close...moreSorry if this has been answered but I couldn’t find the answer. In PAC Control - the Modbus Integration Kit. I noticed the subroutines (like O22Modbus03ReadHoldingRegistersAsInt) don’t appear to close the communication. Would this cause problems If I were to keep calling the SR for new Modbus devices? I guess worst case for me would be 25. Eric... <less DNP3 Configuration for OPTO 22 (S2 and R2) with Schneider Elecetric - ClearSCADA Forum - Published: Hello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA...moreHello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA is the Master. I was able to start the initial communication with the following settings: //Load only the controller running the DNP3 Charts poPAC_DNP_Controller_SNAP_PAC_R2 = &SNAP_R2_8E78;//Load Pointer, This is the Controler With The DNP3 Charts nDNP_Outstation_Address = 20;//Set Outstation Ad...... <less Modbus Master & Slave Communication Forum - Published: Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?...Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?... <less Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
DNP3 Configuration for OPTO 22 (S2 and R2) with Schneider Elecetric - ClearSCADA Forum - Published: Hello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA...moreHello Everyone. I’m having trouble configuring the DNP3 integration kit for the OPTO 22 (using a SNAP-PAC-S2-W and a SNAP-PAC-R2). I’m working with the chart for the Outstation protocol. The ClearSCADA is the Master. I was able to start the initial communication with the following settings: //Load only the controller running the DNP3 Charts poPAC_DNP_Controller_SNAP_PAC_R2 = &SNAP_R2_8E78;//Load Pointer, This is the Controler With The DNP3 Charts nDNP_Outstation_Address = 20;//Set Outstation Ad...... <less Modbus Master & Slave Communication Forum - Published: Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?...Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?... <less Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Modbus Master & Slave Communication Forum - Published: Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?...Hello everyone, I would like to know if it is possible to use both TCP Modbus Master communication on a SNAP PAC R2 PLC and Modbus serial slave communication on a communication module SNAP-SCM 485 ?... <less Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Modbus Communication Forum - Published: Hi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit...moreHi, Do we have any hardware which converts Data From SNAP-PAC-S Series controller or SNAP-PAC- R series controller to Modbus RTU or Modbus TCP-IP. What I know is we can do this with Modbus Integratio Kit through software. Is it any way to do the same with any hardware? Regards, Milind Raval... <less Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Modbus Integration - IEEE 754 Forum - Published: I need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong...moreI need to modify the Modbus integration strategy to accommodate IEEE 754 Float (32 bit) from a Watlow F4T Temperature Humidity controller. Thought i would check here for some ideas before I jump headlong into this and change my brain chemistry forever… Has anyone started this project already?... <less CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
CAN2B Serial Module? Forum - Published: The readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since...moreThe readme for the latest PAC Project refers to 2 new serial modules, including a CAN2B module. I’ve been needing a CANbus solution for a while, so I’m eager to get the details on this product. Since the cat is out of the bag, can you give us the scoop?... <less Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Serial "Master Modbus Configure Port" Subroutine no available for PAC Controls Forum - Published: I’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and...moreI’m in the process of switching over from OptoControls to PAC Controls and everything have converted perfectly expect for the modbus subroutines. I notice there is a new modbus for PAC Controls and notice they dont have a configure port subroutine like my old strategy has. I have downloaded the library “PAC-INT-MB-R9.3a” but it doesn’t seem to include the configure subroutine. This modbus is for serial communication, thanks. OptoContorls Modbus ____________________________PACControls ...... <less SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
SoftPac and Modbus/TCP Forum - Published: Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis...Hello, Can we program SoftPac to be both a Modbus/TCP slave and Modbus/TCP master? It seems the slave part is not native as in the hardware controllers. Regards, Luis... <less LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
LonWorks and Opto Forum - Published: Hi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of...moreHi All I have a question regarding LonWorks and Opto 22. Has any one done any work involving integrating a LonWork system to a PAC controller? I have a particular system where there is a series of LonWorks PLC’s on a network that communicate with the main PC. The PC database (i think its running Schneider TAC) is corrupt and the client is not happy with the current front-end, plus it is going cost a fortune to fix. I have been asked if a solution is feasible based on an Opto 22 PAC system. B...... <less Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Encountered an Improper Argument Forum - Published: Greetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t...moreGreetings, when I tried to create a new numeric variable, I will get an error message ’ Encountered an Improper Argument’ pop out’ in pac control. However, the variable still can be created and doesn’t now effect the running program currently. May I know the reason for the error message coming out and does any solution to avoid it? The program used is pac control professional version r10.3d. Thanks in advance.... <less ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
ModBus to string table? Forum - Published: I am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U...moreI am currently using Modbus with an ABB drive (with a modified version of the Opto Modbus Master kit), but I am running into problems pulling data into the table [U]ntMB_Holding_Register_4X_intM1[/U] due to the fact that some variables are floating and some are integers. Is there a way to pull the data into a String table? Thanks, Nick... <less OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
OPTO22 Website Search Facility Forum - Published: I have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this...moreI have no idea where to put this discussion as there doesn’t seem to be a section to discuss the OPTO22 website and specifically the search facility therein. Please feel free therefore to move this thread to where ever it needs to go. The search facility on the OPTO22 website is an appalling experience. I went to SUPPORT on the website looking for the latest PAC Project Suite software download. I selected DOWNLOADS from the dropdown menu and the page opened on DOWNLOADS. I then went to the filte...... <less Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Modbus RTU Serial Connection Forum - Published: Hi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial...moreHi Brains, I was hoping you could help me with the Modbus Serial Groov Modules. I have two of the modules, and we are trying to connect Modbus through them. What is the IP address of these serial modules? I tried to put in ‘localhost’ but got nothing. Additionally, I noticed that port 502 (seemingly the default port for RTU) was not allowed by default on the Firewall. How could I communicate with these modules? I am wanting to communicate through Groov View and PAC Control PRO. Any advice on the...... <less Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Ethernet-IP communication Snap Pac S2 with M580 Schneider Forum - Published: Hi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication...moreHi, I would like you to help me with a topic. I need to communicate a Snap-Pac-S2 PLC with a Schneider M580 PLC using Ethernet IP protocol. Is this possible? I have used the Ethernet-IP communication between an Allen Bradley Control Logix PLC and a Snap-Pac-S2 PLC and it works very well. I appreciate any help. Thank you very much... <less Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Modbus CHNT DDSU666 power meter Forum - Published: Hello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly...moreHello all! Good day everyone! I have here a power meter that is kind of strange when it comes to its Modbus parameters (or maybe I am doing it wrong). Its name is CHNT DDSU666 power meter, may I kindly ask for some guidance regarding on Modbus for this instrument. I will attach a manual for this specific meter since it is hard to get one. I am using PAC Control to communicate with this meter and an Opto22 Learning Center with SNAP SCM 485-422 module. P.S I am apparently unable to attach a PDF fi...... <less Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Communication with can interface Forum - Published: The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?...The customer has several CAN interface devices. Can I use R1 controller to complete data communication? If I can, what should I do?... <less IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
IO unit communication fail in GRV-EPIC PR2 controller Forum - Published: Hi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried...moreHi all, I am using Groove epic PR2 controller for data communication with Modbus TCP IP device. For this purpose I have tried using MMP. But communication with IO unit is not able to enabled. I tried manually by selecting yes in IO unit page online. But it will automatically goes to NO option. After lot of trials I have shifted to MB Slave chart. But flow is stopped running at waiting for incoming connection command.... <less Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Can2b integration Forum - Published: I am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a...moreI am working on a unit with 2 caterpillar engines, I am wondering if anybody had used pgn 127488 for engine rpm and 127488 for the temperatures and pressures as well as code bits? I am having a thought time getting any data, I am using the Can2b read only kit Thanks... <less Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Modbus/TCP device Forum - Published: Hi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate...moreHi, I don’t see this topic elsewhere, so I am creating it. I have a new feeder, OPTO advised me to use Modbus/TCP, so I ordered it that way. Now I want to connect it without spending an inordinate amount of time. I’ve never programmed Modbus or TCP before but I have successfully handled other serial connections. How should I proceed? Is there a worked example that will let me avoid the wasteful frustrating stage of guessing a command, sending it out, and getting nothing back? I’ve downloaded...... <less Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items
Communication with National Instruments VBAI Forum - Published: National Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module...moreNational Instruments has a machine vision program called Vision Builder for Automated Inspection that offers many of their vision inspection features at a fraction of the full LabVIEW+Vision Module development system cost. In practice, VBAI runs best when it is on a dedicated computer, so that its resources can be focused on image processing and analysis. The results of the image processing would be useful inputs into an Opto22 strategy that controls the equipment on which the vision inspectio...... <less « PreviousPage 2 of 3Next » Show 25 Items Show All Items Show 10 Items Show 25 Items Show 50 Items Show 100 Items